Float Steam Trap With Separator Threaded / Flange ADCA Flt 17

TECHNICAL DESCRIPTION

The float mechanism ensures direct drainage (removal) of the condensate from the steam system. In turn, the automatic air vent ensures the system is freed from uncondensed gases. Float condensate separators are designed primarily for horizontal installation. There are also versions for vertical installation, but the latter are made to order. Condensate separators of this type are designed to operate with a maximum differential pressure of 4.5 Bar. The capacity that is provided can be found in the additional information to the product description.

MAIN FUNCTIONS

To drain (remove) the condensate from the steam installation.

WORKING FLUID / MEDIUM

Steam.

EXECUTION

• SLR version (Steam lock release)
• Regulating needle valve
• Built-in internal filter element
• Installation – horizontal with fluid direction from left to right
• Installation – vertical with fluid direction from top to bottom
• Thermostatic air vent

Dimensions:1/2″ – 2″

Description

The ADCA FLT 17 Float Separator is a high-efficiency industrial separation device designed for removing steam and non-condensable gases from compressed air systems. Engineered with precision threading and flange connections, this separator ensures secure installation and optimal performance in demanding industrial environments. Its robust construction and advanced float mechanism provide reliable operation while maintaining system efficiency and protecting downstream equipment from moisture damage.Key features of the ADCA FLT 17 include:Dual connection options: threaded and flange configurations for versatile installationHigh-capacity separation efficiency for compressed air systemsCorrosion-resistant materials for extended service lifeAutomatic float drainage system for continuous operationPressure-rated design for industrial applicationsLow maintenance requirements and easy service accessThis float separator is ideal for various industrial applications including manufacturing facilities, pneumatic systems, and processing plants where dry, clean compressed air is essential. The ADCA FLT 17 meets industry standards for performance and reliability, making it a critical component for maintaining air system integrity and preventing equipment corrosion. Its design ensures minimal pressure drop while effectively removing contaminants, contributing to overall energy efficiency and reduced operating costs.

Additional information

Materials

No. POSITION MATERIAL
1 Body malleable cast iron GJS-400-15 / 0.7040
2 Lid malleable cast iron GJS-400-15 / 0.7040
3 Gasket stainless steel / graphite
4.1 Seat from DN15 to DN25 stainless steel AISI 410 / 1.4006
4.2 Seat from DN40 to DN50 stainless steel CF8 / 1.4308
5.1 Valve stainless steel AISI 440C / 1.4125
5.2 Valve stainless steel AISI 420C / 1.4021
6 Lever stainless steel AISI 304 / 1.4301
7 Float stainless steel AISI 304 / 1.4301
8 Thermostatic air vent stainless steel (bimetallic)
9 Bolt steel grade 8.8

Features

SPECIFICATION
Standard DIN
Joining standard BSPP thread / Flanged EN1092-2, ANSI 150
Lid connection bolted
Execution straight
Management automatically
Venting automatically
Maximum differential pressure 4.5; 10; 14 Bar
Installation horizontal / vertical
Dimensions
PASSABILITY (kg/h)
MODEL SIZE DIFFERENTIAL PRESSURE (bar)
DN 0.1 0.3 0.5 0.7 1 1.5 2 3 4.5 6 7 8 9 10 12 14
FLT17-4.5 15 - 25 165 205 230 280 330 400 440 535 630 - - - - - - -
FLT17-10 15 - 25 110 130 150 170 200 250 280 340 400 460 495 520 550 595 - -
FLT17-14 15 - 25 80 100 120 140 150 190 220 260 320 380 400 425 440 480 510 550
MODEL SIZE DIFFERENTIAL PRESSURE (bar)
DN 0.1 0.3 0.5 0.7 1 1.5 2 4.5 7 10 12 14
FLT17-4.5 40 - 50 1050 1750 2400 2700 3400 3900 4500 7300 - - - -
FLT17-10 40 - 50 650 1100 1500 1700 2000 2600 3000 4000 5400 6200 - -
FLT17-14 40 - 50 430 720 950 1100 1300 1600 1800 2600 3250 3900 4210 4950