Thermodynamic Threaded / Flanged steam Trap ADCA Dt 42/2

TECHNICAL DESCRIPTION

Thermodynamic condensate traps model ADCA DT 42/2 are compact, lightweight and easy to install and excellent for installation in systems with high operating pressure. Condensate traps of this type have only one moving element and are used in a wide range of operating pressures, without additional adjustment. The connection is threaded or flanged.

MAIN FUNCTIONS

Discontinuous unloading. Operation with superheated steam. Seat and valve can be replaced in place without dismantling the steam trap.
Not affected by hydraulic shocks and vibrations in the system. Built-in filter easy to service.

OPTIONS

• Anti-icing device.

ANNEX

• Saturated and superheated steam.

DIMENSIONS

• threaded ½” ÷ 1″
• flanged DN 15 ÷ DN 25

ACCESSIONS

• threaded ISO 7 / 1 Rp (BS21)
• flanged EN 1092-1 PN40 ÷ PN63 or ANSI.
• welded (on request)

INSTALLATION

• Horizontal installation is recommended.

ANNEX

• Saturated and superheated steam.

RESTRICTIONS

• Minimum operating pressure up to 0.25 Bar
• Maximum operating back pressure up to 80% Bar

Dimensions: 1/2″ – 1″

Description

The ADCA DT 42/2 is a high-performance thermodynamic steam trap designed for efficient and reliable removal of steam in steam systems. Engineered for industrial applications, this trap features a robust construction suitable for both threaded and flanged connections, ensuring compatibility with a wide range of piping configurations. Its thermodynamic operation principle allows for rapid discharge of steam while preventing steam loss, enhancing energy efficiency and reducing operational costs.Key features of the ADCA DT 42/2 include:Durable materials resistant to high temperatures and pressuresCompact design for easy installation in space-constrained environmentsLow maintenance requirements due to minimal moving partsExcellent performance under varying load conditionsCertified to meet industry standards for safety and reliabilityIdeal for use in power plants, manufacturing facilities, and HVAC systems, this steam trap ensures optimal steam system performance. By effectively removing steam, it helps prevent water hammer, corrosion, and equipment damage, thereby extending the lifespan of your steam infrastructure. Choose the ADCA DT 42/2 for a dependable solution that supports continuous operation and energy conservation.

Additional information

Materials

No. POSITION MATERIAL
1 Body P250H / 1.0460
2 Lid AISI 304 / 1.4301 AISI 303 / 1.4305
3 Sealant stainless steel / graphite
4 Saddle hardened stainless steel
5 Valve hardened stainless steel
8 Pipe AISI 304 / 1.4301
9 Filter AISI 304 / 1.4301
10 Gasket stainless steel / graphite
11 Tapa A105 / 1.0432
12 Insulating cap AISI 304 / 1.4301

 

Features

SPECIFICATION
Standard DIN
Joining threaded BSP / flanged
Lid connection threaded cap
Execution straight
Management automatically
Venting with automatic release
Installation horizontal

Flow rate

PASSABILITY (kg/h)
MODEL SIZE DIFFERENTIAL PRESSURE (bar)
DN 1 3 5 7 9 12 15 18 21 24 30 35 42
DT42/2 1/2" - 15 180 250 300 380 430 500 550 590 620 690 730 770 820
DT42/2 3/4” - 20 320 450 530 600 690 720 810 850 900 930 950 980 1040
DT42/2 1” - 25 320 450 530 600 690 720 810 850 900 930 950 980 1040

Limits

MAXIMUM OPERATING PARAMETERS
Maximum working pressure / Bars T max. [°C]
FLANGED PN 63 FLANGE PN 40 / ANSI 300 lb FLANGED ANSI 150 lb
63 bar 40 bar 19.3 bar 50 °C
55.5 bar 35 bar 15.8 bar 150 °C
48 bar 30.4 bar 12.1 bar 250 °C
43.5 bar 27.4 bar 12.1 bar 300 °C
Dimensions
DIMENSIONS (mm)
Threaded or welded (SW) EN PN 16 / PN 40 EN PN 63 ANSI 150 lb ANSI 300 lb
SIZE DN A B C D kg E kg E kg E kg E kg
1/2" - 15 95 60 50 104 1.3 150 2.8 150 3.7 150 2.4 150 2.8
3/4”- 20 95 60 50 104 1.2 150 3.3 150 5.2 150 2.8 150 3.6
1” - 25 95 60 50 110 1.5 160 4 160 6.5 160 3.6 160 4.5